To ensure that the function works for more than one drive at the same time, the terminals for
the corresponding drives must be grouped together as follows:
● 1. Switch-off signal path (CU320)
● 2. switch-off signal path (Motor Module/Power Module with CUA3x)"
The assignment is checked during the test for the switch-off signal paths, The operator
selects "Safe Torque Off" for each group. The check is drive-specific.
Example: Terminal groups
It must be possible to select/deselect "Safe Torque Off" separately for group 1 (drive 1 and
2) and group 2 (drive 3 and 4).
For this purpose, the same grouping for "Safe Torque Off" must be performed on both the
Control Unit and the Motor Modules.
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
9.7 Control signals by way of terminals on the Control Unit and Motor/Power Module
By connecting the binector input to the joint input terminal on the drives in one group.
By appropriately wiring the terminals for the individual Motor Modules/Power Modules
with CUA31/CUA32 assigned to the group.
Note
The grouping must be identical in both monitoring channels.
If a fault in a drive results in a "Safe Torque Off" (STO), this does not automatically mean
that the other drives in the same group also switch to "Safe Torque Off" (STO).
Safety Integrated basic functions
379