6.2

Reference parameters/normalizations

Description
Reference values, corresponding to 100%, are required for the statement of units as
percentages. These reference values are entered in parameters p2000 to p2007. They are
computed during the calculation through p0340 = 1 or in STARTER during drive
configuration. After calculation in the drive, these parameters are automatically protected via
p0573 = 1 from boundary violation through a new calculation (p0340). This eliminates the
need to adjust the references values in a PROFIdrive controller whenever a new calculation
of the reference parameters via p0340 takes place.
Figure 6-1
Note
If a referenced form is selected and the reference parameters (e.g. p2000) are changed
retrospectively, the referenced values of some of the control parameters are also adjusted to
ensure that the control behavior is unaffected.
Using STARTER offline
Following offline drive configuration, the reference parameters are preset; they can be
changed and protected under Drive -> Configuration -> "Disabled list" tab.
Note
If the reference values (p2000 to p2007) are changed offline in STARTER, it can lead to
boundary violations of the parameter values, which cause fault messages during loading to
the drive.
Normalization for vector object
Table 6- 1
Normalization for vector object
Size
Reference speed
Reference voltage
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Illustration of conversion with reference values
Normalization parameter
100 % = p2000
100 % = p2001
6.2 Reference parameters/normalizations
Default at first commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
Basic functions
197