12.4.7

Scaling

Signals for the analog outputs
Table 12- 5
List of signals for analog outputs
Signal
Speed setpoint before the setpoint
filter
Speed actual value motor encoder
Speed actual value
Drive output frequency
Absolute current actual value
Actual DC link voltage value
Total torque setpoint
Actual active power
Control deviation
Modulation depth
Current setpoint, torque-generating
Current actual value, torque-
generating
Flux setpoint
Flux actual value
Speed controller
PI torque output
Speed controller
I torque output
Changing scaling parameters p2000 to p2007
CAUTION
If a referenced form is selected and the reference parameters (e.g. p2000) are changed
retrospectively, the referenced values of some of the control parameters are also adjusted
to ensure that the control behavior is unaffected.
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Parameter
r0060
r0061
r0063
r0066
r0068
r0070
r0079
r0082
r0064
r0074
r0077
r0078
r0083
r0084
r1480
r1482
Basic information about the drive system
12.4 BICO technology: interconnecting signals
Unit
RPM
p2000
RPM
p2000
RPM
p2000
Hz
Reference frequency
Aeff
p2002
V
p2001
Nm
p2003
kW
r2004
RPM
p2000
%
Reference modulation depth
A
p2002
A
p2002
%
Reference flux
%
Reference flux
Nm
p2003
Nm
p2003
Normalization
(100 % = ...)
579