Communication PROFIBUS DP/PROFINET IO
10.1 Communication according to PROFIdrive
Bit
Meaning
12
Master sign of life bit 0
13
Master sign of life bit 1
14
Master sign of life bit 2
15
Master sign of life bit 3
STW1_BM (control word 1, metal industry)
See function diagram [2425].
Table 10- 8
Description of STW1_BM (control word 1, metal industry)
Bit
Meaning
0
ON/OFF1
1
OFF2
Note:
Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
2
OFF3
Note:
Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.
3
Enable operation
4
Enable ramp-function generator
5
Restart ramp-function generator
Note:
The ramp-function generator cannot be frozen via p1141 in jog mode (r0046.31 = 1).
6
Enable speed setpoint
7
Acknowledge fault
Note:
Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.
424
Remarks
User data integrity (4-bit counter)
-
-
-
-
Remarks
0/1
ON
Pulse enable possible
0
OFF1
Braking with the ramp-function generator, then
pulse suppression and switching on inhibited
1
No OFF2
Enable possible
0
Immediate pulse suppression and switching on
inhibited
1
No OFF3
Enable possible
0
Quick stop (OFF3)
Braking with OFF3 ramp p1135, then pulse
suppression and switching on inhibited.
1
Enable operation
Pulse enable possible
0
Disable operation
Cancel pulses
1
Operating condition
Ramp-function generator enable possible
0
Inhibit ramp-function generator
Set ramp-function generator output to zero
1
Restart ramp-function generator
0
Freeze ramp-function generator
1
Enable setpoint
0
Inhibit setpoint
Set ramp-function generator input to zero
0/1
Acknowledge fault
0
No effect
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
BICO
CI: p2045
BICO
BI: p0840
BI: p0844
BI: p0848
BI: p2816.0
BI: p1140
BI: p1141
BI: p1142
BI: p2103