Commissioning
9.2 Test Suite Integrated in the Device
[scgemoaz-210611-01.tif, 1, en_US]
Figure 9-2
Select the previous mode in the working area Device information under Device mode .
Click the Restart button.

Testing Current and Voltage Inputs

9.2.2
If you click in the project tree according to
current values of the measuring points that exist in the device will appear in an editor. On the left side you will
see the phasor diagram for 3-phase analog inputs (absolute value and phase). To the right the measured
values are displayed as numerical values. The primarily measured values for voltage and current are shown as
indicators of absolute value and phase. The reference is the voltage in phase A of measuring point 1. If no
voltage is connected, the current in phase A of measuring point 1 serves as the reference. All indicated phasor
values refer to the reference quantities.
You can identify and verify the following errors with measured-value control:
Turner in the analog wiring
Vector group
Direction between current and voltage
Devices connected via effective connections can also represent analog measuring points of remote ends as
phasors. In this case, the phasors of measuring points of up to 6 remote ends are shown. For example, the
stability of a line differential protection can thus be verified.
[sctstane-140211-01.tif, 1, en_US]
Figure 9-3
232
Top Rail in the Working Window
Figure 9-1
Example of a Check of Analog Inputs
on the menu item Analog inputs, a visualization of the
C53000-G5040-C003-J, Edition 07.2022
SIPROTEC 5, Operation, Manual