10.2.3 Connection with Stepping Motor Driver
Connections of each signal and precautions
Signal type
Pulse command output
Home input
Near home input
CCW over limit input
CW over limit input
KEY POINTS
•
Use twisted-pair cables for the connection between the unit and motor
driver.
•
Connect each signal to the terminal numbers allocated in the I/O terminal
allocation screen of "Positioning" in the Multi I/O Unit Setting of FPWIN GR7.
Terminal numbers and I/O numbers allocated to each signal vary according
•
to the settings. Each setting is configured in the "Multi I/O Unit Setting"
dialog box of FPWIN GR7. Refer to "10.4 Setting of Positioning Function".
Point
Connect the output allocated to each channel and the command pulse input of
motor driver.
Use twisted-pair cables for the connection.
Use a 24 VDC input for the input on the driver side. When the input interface of the
driver is 5 VDC input, insert a resistor for limiting currents externally.
Connect the input allocated to each channel and the home sensor.
Use twisted-pair cables for the connection.
Connect the near home sensor.
Connect the over limit switches.