Panasonic FP7 User Manual page 91

Multi input/output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

5. Press the [OK] button.
The selected condition will be registered on the "Multi I/O Unit Setting" dialog box.
The following figure shows the example that "Pulse output (Direction distinction)"
is allocated to the outputs (Y108-Y109) of multi I/O unit. The control inputs for
monitoring are allocated to the inputs of the unit internal I/O (X118-X119), and the
control output is allocated to the outputs (Y118/Y11C/Y128/Y12C) automatically.
The set values will be effective when they are downloaded with programs or other
configuration information as a project.
 Setting of counter elapsed value
The values set in the "Pulse output Advanced" dialog box are reflected as follows.
Item
PLS/PWM counter
elapsed value
(Note): The values in "PLS/PWM counter elapsed value area" of the channel to which the positioning function has
been set with the H type are the same as the values in "positioning elapsed value (current value) area".
REFERENCE
This function can also be set by writing to unit memories with user
programs. For details of unit memories, refer to "13.4.8 Pulse Output / PWM
Output Setting Area".
Operation
The value set in the "Counter elapsed value" in the dialog
box is set in the PLS/PWM counter elapsed value area after
switching the mode to RUN mode.
9.1 Pulse Output / PWM Output Function
Related unit memory
UM00170-UM00177
9-5