Troubleshooting

12.2.3 ERR LED is Flashing on the Unit

 Situation
A warning occurred. The setting content is wrong. A warning also occurs in the initial state at
the time of factory shipment as the output setting is not configured.
 Solution
Check the condition according to the following procedure.
PROCEDURE
1. Select "Online" > "Device Monitor" in FPWIN GR7.
2. Monitor the unit memory (UM00065) and confirm the warning code.
3. Check the appropriate way to handle for each warning code, switch the
mode to PROG. mode and review the settings or program.
4. Switch the mode to RUN mode. Once the ERR.LED turns off, the warning
state will be cleared. If the LED does not turn off, repeat the above operation.
 Warning code
Code
Name
Interrupt
U1
setting
error
Output
U2
setting
error
Input
voltage
U3
setting
error
Pulse
output
U4
setting
error
PWM
frequency
U5
setting
error
 Cancel of warning annunciation setting
To make warnings not to be announced, set "Warning annunciation" to "Not announce" in the
"Multi I/O Unit Setting" screen of tool software FPWN GR7. (Available since Ver.1.1.) Or, set
the bit 9 of UM00062 to 1.
12-8
Situation
As the interrupt switch is not set, the
interrupt function is not activated.
Output polarities are mixed.
This error occurs when the sink output,
source output, push-pull output (negative
logic), or push-pull (positive logic) are
mixed.
The input voltage is set by two points.
A value exceeding the operation
guarantee range (over 500,001) is set.
A value exceeding the settable range
(over 100,001) is set.
Solution
Turn on the mode setting switch no. 1 of
the unit to enable the interrupt function.
This is a warning to check if the wiring is
correct.
If you do not want to announce warnings,
set "Warning annunciation" to "Not
announce" using the tool software or
program.
Set the input voltage on a program by
four points.
Monitor the unit memory
(UM0015E/UM0015F) in which the pulse
output flag is stored, and review the
settings after confirming the detailed
information.
Review the set value.