Unit Memory Detailed Information; Alarm/Error/Warning - Panasonic FP7 User Manual

Multi input/output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

13.4 Unit Memory Detailed Information

13.4.1 Alarm/Error/Warning

 Error alarm setting
Unit
memory no.
Name
(Hex)
UM 00062
Error alarm setting
Setting value (UM 00062)
Bit no.
Settings
b0-b7
(Reserved for system)
Double word access
b8
error annunciation
b9
Warning annunciation
b10-b15
(Reserved for system)
(Note): It is set in the "Multi I/O Unit Setting" screen of tool software FPWIN GR7 (Available since Ver.1.1) or using a
user program.
 Alarm / Error / Warning codes
Unit
memory no.
Name
(Hex)
Double word access
UM 00063
error occurrence address
Unit alarm code (H type
only)
UM 00064
Unit error code 1
UM 00065
Unit warning code
UM 00066
Unit error code 2
13.4 Unit Memory Detailed Information
Setting range and description
Set whether or not to announce abnormality when a double word
access error or warning occurs.
Default
Setting range and description
-
-
0: Announce
0: Announce
1: Not announce
0: Announce
0: Announce
1: Not announce
-
-
Setting range and description
Stores the address of a user program that an abnormal
access was made when the double word access error has
occurred.
Stores the alarm code when the followng alarm occurs.
U20: Unit alarm
Stores the error code when the following error occurs.
U1: Double word access error
Stores the warning codes when the following warnings
occur.
U1: Interrupt setting error
U2: Output setting error
U3: Input voltage setting error
U4: Pulse output setting error
U5: PWM output setting error
Stores the error codes when the following errors occur.
U26: System error
U44: Positioning error
U45: Unit processing error
R
W
-
-
A
A
A
A
-
-
R
W
A
-
A
-
A
-
A
-
A
-
13-27