Output Specifications - Panasonic FP7 User Manual

Multi input/output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

Input/Output Specifications and Wiring

3.1.4 Output Specifications

Item
Insulation system
Output device
Output method (Note 1)
Rated load voltage
Allowable load voltage range
Max. load current
Off state leakage current
ON Max. voltage drop
OFF→ON
Response
time
ON→OFF
Voltage
External
power supply
Current
Output points per common
Surge absorber
Operating mode indicator
(Note 1): The output method is selected by the software. The both polarities are off at the time of startup. The output
polarity must be set.
(Note 2): It shows the response time when the push-pull method is set and the output current is 0.1 A. It varies
according to the setting of the output method and loads.
(Note 3): The voltages of the external power supply of output circuit and the power supply for the load circuit should
be within the range of 5 to 24 V. When supplying power for the external power supply and that for the load
circuit from other power supplies, the load circuit voltage (V2) must be the same as or smaller than the external
supply voltage (V1). When the load circuit voltage (V2) is larger than the external supply voltage (V1), the
current flows back as below.
In the case of sink output
+
Yn
-
3-6
Digital isolator
MOSFET
Nch open drain / Pch open drain / Push-pull
5 V DC to 24 V DC
4.75 V DC to 26.4 V DC
0.1 A
3.0 µA or less
1.0 V DC or less
0.5 µs or less (Note 2)
0.5 µs or less (Note 2)
4.75 V DC to 26.4 V DC
100 mA or less
16 points/common (common to external power supply terminals)
Zener diode
LED display
L
V1
V2
Specifications
In the case of source output
+
Yn
L
-
V2
V1

Advertisement