Panasonic FP7 User Manual page 43

Multi input/output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

 Basic setting item
Setting
Default
item
Double word
error
Announce
annunciation
Warning
Announce
annunciation
Input voltage
5V-24V
mode
Input time
2µs
constant
Output
terminal
Output Off
polarity
(Note): The parameters of the basic setup are set for the external terminal regardless of the selection contents of
functions.
Precautions when using FPWIN GR7 for configuration
When using the GR7 ver.2.12 or later on the Multi I/O Unit ver.1.0x, there are the following
restrictions.
• On the Multi I/O Unit ver.1.0x, the setting of the double word error annunciation specified by
the FPWIN GR7 is not reflected . It can be set using a program. Refer to Chapter 13.4.1.
• On the Multi I/O Unit ver.1.0x, the following values specified for input time constants by the
FPWIN GR7 are set as 2 µs.
0.5 μs / 1.5 μs / 32 μs / 64 μs / 96 μs / 128 μs / 256 μs / 8 ms
They can be set using a program. Refer to Chapter 13.4.2.
Settings
Set whether or not to announce a double word access error
when it occurs.
Announce / Not announce
Set whether or not to announce a warning when it occurs.
Announce / Not announce
Select either the 5V-24V mode or 12V-24V mode.
The switching operation of the impedance of the input circuit,
minimum ON voltage and maximum ON voltage vary
according to the selected mode.
0 / 0.5μs / 1μs / 1.5μs / 2μs / 4μs / 8μs / 16μs / 32μs / 64μs /
96μs / 128μs / 256μs / 2ms / 4ms / 8ms
The output circuit is switched. Select to match the actual
wiring.
Output Off Output Off
Sink output: Nch output
Source output: Pch output
N-type push-pull: Push-pull (Negative logic)
P-type push-pull: Push-pull (Positive logic)
5.1 Basic Setup
Related
page
P.12-4
P.12-8
P.3-4
P.3-4
P.3-6
5-3