Irig-B - GE B90 UR Series Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90 UR Series:
Table of Contents

Advertisement

3 HARDWARE
3.2 WIRING

3.2.8 IRIG-B

IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes that can be either DC level shifted or ampli-
tude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment can use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can be synchronized.
3
Figure 3–24: IRIG-B CONNECTION
Using an amplitude modulated receiver causes errors up to 1 ms in event time-stamping.
NOTE
GE Multilin
B90 Low Impedance Bus Differential System
3-25

Advertisement