Settable buffer time by DIP switches in the range between 5 to 315 sec. or
up to enforced shutdown by deep discharging.
S
In case of increased load current requirements (e.g. when connecting incan-
descent lamps, contactor relays with DC autotransformer winding, DC mo-
tors, DC/DC converters, electronic modules with high input capacity), high,
electronically limited peak currents are delivered automatically.
S
After a power failure, the battery module is automatically electronically dis-
connected from the loads and quickly recharged with a constant current of
0.7A (U/I characteristic with 27V end-of-charge voltage).
S
Exhaustive discharge protection
S
ON/OFF control circuit
S
Signaling
S
LED green/LED yellow and floating changer for mains/battery operation
S
LED red and floating changer for readiness for backup existing (LED OFF)/
alarm (LED ON).
S
RS-232 interface (serial interface) for the additional output of all signals to a
PC.
The connection from the SITOP POWER DC-UPS module 15 to the serial inter-
face of the PC is made using a 9-pin SUB-D interconnecting cable:
S
Design connector/socket connector
S
The individual cables are connected 1:1 to the appropriate pins.
Table 2-14
Pin assignment of the 9-pin SUB-D connectors
Pin
Signal
2
RxD
3
TxD
7
RTS
2 Hardware Descriptions
2.11 Uninterruptible power supply (UPS)
Designation
Data cable
Negative supply voltage
Positive supply voltage
2-91