7 PROFIBUS DP Communication
7.3 SIMATIC S7 project
Configuring the
PLC
Parameterizing the
MPI interface
Dialog
7-214
After DP master has been configured, 840Di Rack with PROFIBUS DP is now
displayed in the Station window.
You can use the axis start-up tool SimoCom U to start up all DP slaves 611U
connected to PROFIBUS from a SINUMERIK 840Di. To allow this, the PLC
must route SimoCom U to PROFIBUS. This requires that the MPI interface of
the PLC is networked.
To do so, open the Properties dialog box by double-clicking on the PLC in 840Di
Rack.
The following settings are made in the dialog box:
S
Interface type
S
Address
S
Data transfer rate.
Dialog: Properties of PLC315-2DP M/S 2AF03
Tab: General
Group: Interface
Button: "Properties..."
Dialog: Properties – MPI Interface PLC315-2DP M/S 2AF03
Tab: Parameters
Address: 2 (see Note)
Subnetwork: MPI
Button: "Properties..."
Dialog: Properties – MPI
Tab "Network Settings"
Data transfer rate: 1.5 Mbps
OK
OK
OK
Notice
With SINUMERIK 840Di, the MPI address of the PLC must always be set to "2".
 Siemens AG, 2003. All rights reserved
SINUMERIK 840Di Manual (HBI) – 06.03 Edition