How to Programme
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameter's value is changed back to factory
setting's value from another different value, the parameter
will NOT be listed in Changes Made.
1.
Press [Menu] to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
] [
] to select either FC 101 wizard,
closed loop setup, motor setup or changes made,
then press [OK].
3.
Press [
] [
] to browse through the parameters
in the Quick Menu.
4.
Press [Ok] to select a parameter.
5.
Press [
] [
] to change the value of a parameter
setting.
6.
Press [Ok] to accept the change.
7.
Press either [Back] twice to enter "Status", or
press [Menu] once to enter "Main Menu".

6.3.4 Main Menu

[Main Menu] is used for programming all parameters. The
Main Menu parameters can be accessed immediately
unless a password has been created via 0-60 Main Menu
Password. For the majority of VLT
applications it is not necessary to access the Main Menu
parameters but instead the Quick Menu provides the
simplest and quickest access to the typical required
parameters.
The Main Menu accesses all parameters.
1.
Press [Menu] until indicator in display is placed
above "Main Menu".
2.
Use [
] [
] to browse through the parameter
groups.
3.
Press [Ok] to select a parameter group.
4.
Use [
] [
] to browse through the parameters in
the specific group.
5.
Press [Ok] to select the parameter.
6.
Use [
] [
] to set/change the parameter value.
[Back] is used to go one level back.
®
VLT
HVAC Basic Drive Design Guide
®
HVAC Basic Drive
®
MG18C402 - VLT
is a registered Danfoss trademark
6.4 Quick Transfer of Parameter Settings
between Multiple Frequency Converters
Once the set-up of a frequency converter is complete,
Danfoss recommends to store the data in the LCP or on a
PC via MCT 10 Setup Software tool.
Data storage in LCP.
WARNING
Stop the motor before performing this operation.
1.
Go to 0-50 LCP Copy
2.
Press the [Ok] key
3.
Select "All to LCP"
4.
Press the [Ok] key
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter:
NOTE
Stop the motor before performing this operation.
1.
Go to 0-50 LCP Copy
2.
Press the [Ok] key
3.
Select "All from LCP"
4.
Press the [Ok] key
6.5 Read-out and Programming of Indexed
Parameters
Use as an example.
Choose the parameter, press [Ok], and press [
scroll through the indexed values. To change the
parameter value, select the indexed value and press [Ok].
Change the value by pressing [
the new setting. Press [Cancel] to abort. Press [Back] to
leave the parameter.
]/[
] to
]/[
]. Press [Ok] to accept
75
6
6