B.3 Parameter Table
No.(Addr.)
Name
E2-03
Motor No-Load Current
(310H)
E2-04
Number of Motor Poles
(311H)
E2-05
Motor Line-to-Line Resistance
(312H)
E2-06
Motor Leakage Inductance
(313H)
E2-07
Motor Iron-Core Saturation
(314H)
Coefficient 1
E2-08
Motor Iron-Core Saturation
(315H)
Coefficient 2
E2-09
Motor Mechanical Loss
(316H)
E2-10
Motor Iron Loss for Torque
(317H)
Compensation
E2-11
Motor Rated Power
(318H)
<4> Default setting value varies by the drive model (o2-04).
u F: Simple Feedback Settings
n
F1: PG Settings
These parameters determine drive behaviour when using the simple PG feedback function. Note that the pulse signal is
input to the pulse train input terminal RP and must be configured in the H6-
No.(Addr.)
Name
F1-02
Operation Selection at PG Open
(381H)
Circuit (PGo)
F1-03
Operation Selection at Overspeed
(382H)
(oS)
F1-04
Operation Selection at Deviation
(383H)
F1-08
Overspeed Detection Level
(387H)
F1-09
Overspeed Detection Delay Time
(388H)
F1-10
Excessive Speed Deviation
(389H)
Detection Level
F1-11
Excessive Speed Deviation
(38AH)
Detection Delay Time
F1-14
PG Open-Circuit Detection Time
(38DH)
230
All Modes
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
All Modes
Sets the number of motor poles. Automatically set during Auto-Tuning.
All Modes
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
All Modes
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
Automatically set during Auto-Tuning.
V/f
OLV
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
OLV
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during
Auto-Tuning.
V/f
OLV
Sets the motor mechanical loss as a percentage of motor rated power (kW).
V/f
OLV
Sets the motor iron loss.
All Modes
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
V/f
OLV
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Emergency Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
V/f
OLV
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Emergency Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
V/f
OLV
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Emergency Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
V/f
OLV
Sets the overspeed detection level as a percentage of the maximum output frequency.
V/f
OLV
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
V/f
OLV
Sets the speed deviation detection level as a percentage of the maximum output frequency.
V/f
OLV
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv).
V/f
OLV
Sets the time required to trigger a PG Open fault (PGo).
YASKAWA EUROPE SIEP
Description
parameter group.
Description
V/f w PG
OLV w PG
V/f w PG
OLV w PG
V/f w PG
OLV w PG
V/f w PG
OLV w PG
V/f w PG
OLV w PG
V/f w PG
OLV w PG
V/f w PG
OLV w PG
V/f w PG
OLV w PG
Setting
common_
Default:
<4>
TMonly
Min: 0 A
Max: E2-01
common_
Default: 4
TMonly
Min: 2
Max: 48
common_
Default:
<4>
Min: 0.000 Ω
TMonly
Max: 65.000 Ω
common_
Default:
<4>
TMonly
Min: 0.0%
Max: 40.0%
common_
Default: 0.50
TMonly
Min: 0.00
Max: 0.50
common_
Default: 0.75
TMonly
Min: E2-07
Max: 0.75
common_
Default: 0.0%
TMonly
Min: 0.0%
Max: 10.0%
common_
Default:
<4>
TMonly
Min: 0 W
Max: 65535 W
common_
Default:
<4>
TMonly
Min: 0.00 kW
Max: 650.00 kW
Setting
common_
TMonly
Default: 1
Min: 0
Max: 3
common_
TMonly
Default: 1
Min: 0
Max: 3
common_
TMonly
Default: 3
Min: 0
Max: 3
common_
Default: 115%
TMonly
Min: 0%
Max: 120%
common_
Default: 0.0 s
TMonly
Min: 0.0 s
Max: 2.0 s
common_
Default: 10%
TMonly
Min: 0%
Max: 50%
common_
Default: 0.5 s
TMonly
Min: 0.0 s
Max: 10.0 s
common_
Default: 2.0 s
TMonly
Min: 0.0 s
Max: 10.0 s