u H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
n
H1: Multi-Function Digital Inputs
No.(Addr.)
Name
H1-03
Terminal S3 Function Selection
(400H)
H1-04
Terminal S4 Function Selection
(401H)
H1-05
Terminal S5 Function Selection
(402H)
H1-06
Terminal S6 Function Selection
(403H)
H1-07
Terminal S7 Function Selection
(404H)
<19> With the speed reference priority d1-18 set to 0, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7 are: 24,
13, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F respectively.
H1-
Function
Setting
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
7
Accel/decel Ramp Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
F
Not Used (Through Mode)
14
Fault Reset
15
Emergency Stop (N.O.)
17
Emergency Stop (N.C.)
18
Timer Function Input
1A
Accel/decel Ramp Selection 2
YASKAWA EUROPE SIEP
All Modes
Assigns a function to the multi-function digital inputs.
Refer to page
231
to page
232
for a description of setting values.
Note: Unused terminals should be set to F.
H1 Multi-Function Digital Input Settings
All Modes
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
terminals will create a multi-step speed sequence using the speed references set in d1-01 through d1-08.
All Modes
Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in C1-03, C1-04).
When combined with another input terminal set for "Accel/Decel ramp 2" (H1-
switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in C1-07, C1-08).
All Modes
Closed: No drive output
All Modes
Open: No drive output
All Modes
Select this setting when using the terminal in a pass-through mode. The terminal does not trigger a drive function
but can be used as digital input for the controller the drive is connected to.
All Modes
Closed: Resets faults if the cause is cleared and the Up/Down command is removed.
All Modes
Closed: Decelerates to stop at the Emergency Stop ramp set to C1-09.
All Modes
Open: Decelerates to stop at the Emergency Stop ramp set to C1-09.
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2-
= 12).
All Modes
Used in conjunction with an input terminal set for "Accel/decel ramp selection 1" (H1-
drive to switch between accel/decel ramp 3 and 4.
YASKAWA AC Drive L1000V Technical Manual
Description
Description
B.3 Parameter Table
Setting
Page
Default:
<19>
Min: 3
124
Max: 79
Default:
<19>
Min: 3
124
Max: 79
common_
TMonly
Default:
<19>
Min: 3
124
Max: 79
Default:
<19>
Min: 3
124
Max: 79
Default:
<19>
Min: 3
124
Max: 79
Page
124
common_
TMonly
124
124
common_
TMonly
124
= 1A), the drive can also
common_
TMonly
124
common_
TMonly
124
common_
TMonly
124
common_
TMonly
125
common_
TMonly
125
common_
TMonly
125
common_
TMonly
125
common_
TMonly
125
= 7), and allows the
B
231