u Inspection Operation
n
Start Condition in Inspection Operation
Inspection operation is performed when an Up or Down signal is input while one of the following conditions is true:
• Parameter d1-18 is set to 0 or 3 and the selected speed is higher than d1-28 but lower than d1-29.
• Parameter d1-18 is set to 1 or 2 and a digital input programmed for Inspection Operation Speed (H1-
enabled.
Inspection Operation uses the same acceleration characteristics and brake sequence at start as normal operation.
The carrier frequency is set to 2 kHz during Inspection Operation, but can be changed using parameter C6-21.
n
Stop Condition in Inspection Operation
To stop the drive during Inspection Operation, either remove the Up or Down command or reset the input terminal for

Inspection Operation.

A deceleration ramp can be set for Inspection Operation using parameter C1-15.
• If C1-15 = 0.00, the drive immediately applies the brake, shuts off the drive output, and opens the motor contactor, i.e.,
the multi-function output terminals set for "Brake Control" (H2-
51) are cleared.
• If C1-15 > 0.00, the drive decelerates to stop at the rate set to C1-15, then applies the brake, shuts the output off, and
opens the motor contactor.
n
Inspection Operation Timing Chart
A timing chart for Inspection Operation appears in
Inspection Operation without Decel Ramp (C1-15=0)
Safe disable (terminals H1/H2 on)
and Baseblock off (H1-
H1-
= 54 (Inspection Operation)
Up/Down command
H2-
= 51 (Output Cont. Contr.)
H2-
= 50 (Brake Control)
<1> The drive stops if either the Up/Down command or Inspection Operation signals are removed.
YASKAWA EUROPE SIEP
Figure
Inspection Operation
Speed
DC Injection Braking/
Position Lock at start
Speed
=8/9)
<1>
Figure 4.11 Inspection Operation Sequence
YASKAWA AC Drive L1000V Technical Manual
4.6 Setup Procedure for Elevator Applications
= 50) and "Output Contactor Control" (H2-
4.11.
Inspection Operation with Decel Ramp (C1-15>0)
Speed
Safe disable (terminals H1/H2 on)
and Baseblock off (H1-
=8/9)
H1-
= 54 (Inspection Operation)
Up/Down command
H2-
= 51 (Output Cont. Contr.)
H2-
= 50 (Brake Control)
= 54) is
Inspection Operation
Speed
DC Injection Braking/
C1-15
Position Lock at start
<1>
=