Setting 2F: Maintenance period
Output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as
determined by the estimated performance life span of those components. Component performance life is displayed as a
percentage on the digital operator screen. Refer to
Setting 30: During torque limit
Output closes when the motor is operating at the torque limit specified by the L7-
This setting can only be used in OLV, CLV and CLV/PM control modes. Refer to
page 144
for details.
Setting 37: During frequency output
Output closes when the drive is outputting a frequency.
Status
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
Figure 5.22
Up/Down command
Setting 50: Brake control
This setting can be used in the brake sequence for the elevator application. Closing the output terminal should cause the
brake to release, and opening the terminal should apply the brake. Refer to
Setting 51: Output contactor control
Assigning this command to an output terminal can send a signal to the controller to close the output contactor. The output
contactor should open when the terminal is released.
Setting 54: Light load direction
Indicates the light load direction detected during emergency operation with light load search. When the terminal is closed
the light load direction is up, when it is open the light load direction is down. Refer to
Function on page 94
for details.
Setting 55: Light load direction detection status
This terminal is open during Light Load Direction Search. When the search function is complete, the terminal closes.
Refer to
Light Load Direction Search Function on page 94
Setting 58: Safe disable status
This terminal closes if the Safe Disable inputs H1-HC are closed and opens when terminals H1-HC are open.
Note: This digital output function is only available on L1000V drives with firmware version 7011 and later.
Setting 100 to 158: Functions 0 to 58 with Inverse Output
These settings have the same function as settings 0 to 58 but with inverse output. Set as 1
inverse output and the last two digits specify the setting number of the function.
Examples:
• For inverse output of "8: During baseblock", set 108.
YASKAWA EUROPE SIEP
Periodic Maintenance on page 195
OFF
ON
Baseblock
OFF
command
Output
frequency
OFF
ON
During run
OFF
ON
During frequency
Output
Figure 5.22 During Frequency Output Time Chart
YASKAWA AC Drive L1000V Technical Manual
parameters or an analog input.
L7-01 to L7-04: Torque Limits on
Description
ON
Brake Sequence on page 90
Light Load Direction Search
for details.
5.7 H: Terminal Functions
for details.
common_
TMonly
for details.
, where the "1" indicates
5
133