3.3
Main Circuit Connection Diagram
Refer to
Figure 3.2
when wiring the main circuit of the drive. The power supply for the main circuit also provides power
to the control circuit.
NOTICE: Do not use the negative DC bus terminal "-" as a ground terminal. This terminal is at high DC voltage potential. Improper
wiring connections could damage the drive.
NOTICE: When installing an optional DC Reactor, remove the jumper between main circuit terminals +1 and +2.
u Three-Phase 200 V Class (CIMR-LC2V0018B to 2V0060F)
Three-Phase 400 V Class (CIMR-LC4V0009B to 4V0031F)
Figure 3.2
YASKAWA EUROPE SIEP
DC reactor
Jumper
Three-Phase Supply
200 Vac (400 Vac)
Figure 3.2 Connecting Main Circuit Terminals
YASKAWA AC Drive L1000V Technical Manual
3.3 Main Circuit Connection Diagram
Braking
Resistor Unit
(option)
(option)
+2
+1
B1 B2
Drive
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
—
Motor