4.6 Setup Procedure for Elevator Applications
Select the configuration that matches your application. Follow the corresponding instructions for wiring and drive
settings. For configurations not covered in the list above, contact your Yaskawa representative or our sales office directly
for consultation.
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Never remove or install option cards
or attempt to replace the cooling fan while the drive is switched on. Make sure that the drive and all devices connected to the drive
have been shut off prior to performing and type of maintenance or wiring. After shutting off the power, wait for at least the amount of
time specified on the drive before touching any components or perform wiring. The internal capacitor remains charged even after the
power supply is turned off.
NOTICE: Be sure to thoroughly read the instructions for wiring and magnetic contactor sequence described in this section before
setting up the drive for Rescue Operation. Failure to follow these instructions can damage the drive.
NOTICE: Refrain from using Rescue Operation for extend periods of time. Rescue Operation uses a low DC bus voltage, which can
cause the cooling fan to shut off temporarily during Rescue Operation. Continuing to operate under these conditions can trigger an
overheat fault and damage the drive.
n
Using a Single-Phase, 230 Vac UPS (Uninterruptable Power Supply)
Follow the instructions when using a single-phase 230 V UPS for Rescue Operation. A 230 V UPS can be used for both
200 V and 400 V class drives.
Wiring
Refer to
Figure 4.13
for a wiring diagram.
Figure 4.12
N
L1
L2
L3
Operation Sequence
Starting Rescue Operation
1. Open contactor B.
2. Set the input terminal programmed for Rescue Operation (H1-
3. Close contactor A.
4. Set the Up/Down command.
92
Elevat or
cont rol
Magnetic
syst em
Contactor A
UPS
sine wave
230 Vac
single-phase
Magnetic
Contactor B
H1-
= 55
(Rescue Operation)
Magnetic Contactor Sequence
Magnetic Contactor B
Magnetic Contactor A
H1-
= 55
(Rescue Operation)
Figure 4.13 Using a Single-Phase 230 V UPS
YASKAWA EUROPE SIEP
L1000V
B2
B1
+1
+2
R/L1
S/L2
T/L3
-
S
to S
3
7
SC
= 55).
U/T1
V/T2
W/T3
YASKAWA AC Drive L1000V Technical Manual