A.3 Drive Specifications
A.3 Drive Specifications
Note: 1. Perform rotational Auto-Tuning to obtain the performance specifications given below.
2. For optimum performance life, install the drive in an environment that meets the required specifications.
Item
Control Method
Frequency Control Range
Frequency Accuracy
(Temperature Fluctuation)
Frequency Setting Resolution
Output Frequency Calculation
Resolution
Frequency Setting Signal
Starting Torque
Control
Speed Control Range
Characteristics
Speed Control Accuracy
Speed Response
Torque Limit
Accel/Decel Ramp
Braking Transistor
V/f Characteristics
Main Control Functions
Motor Protection
Momentary Overcurrent Protection
Overload Protection
Overvoltage Protection
Protection
Functions
Undervoltage Protection
Heatsink Overheat Protection
Stall Prevention
Ground Protection
DC Bus Charge LED
Area of Use
Ambient Temperature
Humidity
Environment
Storage Temperature
Altitude
Vibration / Shock
Safety Standard
Protection Design
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different
motors and with changing motor temperature.
<2> Overload protection may be triggered when operating with 165% of the rated output current if the output speed is less than 6 Hz.
<3> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
218
The following control methods can be set using drive parameters:
• V/f Control (V/f)
• V/f Control with simple PG (V/f w/ PG)
• Open Loop Vector Control (OLV)
• Open Loop Vector Control with simple PG (OLV w/ PG)
0.01 to 120 Hz
Digital input: within ±0.01% of the max output speed (-10 to +50 °C)
Analog input: within ±0.1% of the max output speed (25°C ±10 °C)
Digital inputs: 0.01 Hz
1/2
20
x Maximum Output Frequency (E1-04)
Digital Inputs (Multi-Step Speed Selection)
V/f: 150% at 3 Hz
<1>
OLV: 200% at 0.3 Hz
V/f: 1:40
<1>
OLV: 1:100
V/f: ±2.0 % (25°C ±10 °C), V/f w/ PG: ±0,03 % (25°C ±10 °C)
<1>
OLV: ±0.2% (25°C ±10 °C), OLV w/ PG: ±0.03% (25°C ±10 °C)
V/f: 3.0 Hz
<1>
OLV: 10 Hz
Parameters setting allow separate limits in four quadrants (available in OLV only
0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings, unit changeable to m/s
2
ft/s
)
Built-in on all models.
Freely programmable
Inertia Compensation, Overtorque/Undertorque Detection, Torque Limit, Speed Reference, Accel/decel Switch, 5 Zone Jerk
Settings, Auto-Tuning (Stationary and Rotational), Dwell, Cooling Fan on/off Switch, Slip Compensation, Torque
Compensation, DC Injection Braking at Start and Stop, Fault Reset, Removable Terminal Block with Parameter Backup
Function, High Frequency Injection, Short Floor Operation, Rescue Operation (Light Load Direction Search Function),
Inspection Run, Elevator Brake Sequence, Speed related parameters with elevator units display, etc.
Electronic thermal overload relay
Drive stops when output current exceeds 200% of rated output current
Drive stops after 30 s at 165% of rated output current
200 V class: Stops when DC bus voltage exceeds approx. 410 V
400 V class: Stops when DC bus voltage exceeds approx. 820 V
200 V class: Stops when DC bus voltage falls below approx. 190 V (except in Rescue Operation)
400 V class: Stops when DC bus voltage falls below approx. 380 V (except in Rescue Operation)
Thermistor
Stall Prevention is available during acceleration, and during run.
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
-10 to 50 °C
95 RH% or less (no condensation)
20 to 60 °C (short-term temperature during transportation)
-
Up to 1000 meters without derating, up to 3000m with output current and voltage derating
10 to 20 Hz: 9.8 m/s
2
2
20 to 55 Hz: 5.9 m/s
One Safe Disable input according to ISO13849-1 Cat.3 PLd, IEC61508 SIL2. Time from input open to drive output stop is less
than 1 ms.
IP20 enclosure
YASKAWA EUROPE SIEP
Specification
<2>
<3>
YASKAWA AC Drive L1000V Technical Manual