YASKAWA L1000V Technical Manual page 145

200/400 v classes: 4.0 to 15 kw
Hide thumbs Also See for L1000V:
Table of Contents

Advertisement

n
L8-03: Overheat Pre-Alarm Operation Selection
Sets the operation when an overheat pre-alarm is detected.
No.
L8-03
Setting 0: Ramp to stop
If an overheat alarm occurs, the drive decelerates to stop using the deceleration ramp currently selected. If a digital
output is programmed for "fault" (H2-
Setting 1: Coast to stop
If heatsink overheat (oH) occurs, the drive switches off the output and the motor coasts to stop. If a digital output is
programmed for "fault" (H2-
Setting 2: Fast Stop
If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop ramp (C1-09). If a digital output is
programmed for "fault" (H2-
Setting 3: Alarm only
If an overheat alarm occurs, an alarm is output and the drive continues operation.
Setting 4: Run at Frequency set to L8-19
If an overheat alarm occurs, the drive will lower the output frequency according to the rate set in parameter L8-19.
n
L8-05: Input Phase Loss Protection Selection
Enables or disables the input phase loss detection.
No.
L8-05
Setting 0: Disabled
Setting 1: Enabled
n
L8-07: Output Phase Loss Protection
Enables or disables the output phase loss detection, which is triggered when the output current falls below 5% of the
drive rated current.
Note: Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating.
Disable this parameter in such cases.
No.
L8-07
Setting 0: Disabled
Setting 1: Fault when one phase is lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to
stop.
Setting 2: Fault when two phases are lost
An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to
stop.
YASKAWA EUROPE SIEP
Name
Overheat Pre-Alarm Operation Selection
= E), this output will be triggered.
= E), this output will be triggered.
= E), this output will be triggered.
Name
Input Phase Loss Protection Selection
Name
Output Phase Loss Protection
YASKAWA AC Drive L1000V Technical Manual
5.8 L: Protection Functions
Setting Range
Default
0 to 4
Setting Range
Default
0 to 1
Determined by o2-04
Setting Range
Default
0 to 2
3
1
5
145