5.10 o: Operator Related Settings
Setting 0: No change (awaiting command)
Setting 1: Set User Initialize values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing
the ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for "User Initialize" are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values
and returns the display to 0.
n
o2-04: Drive Model Selection
This parameter must be set when replacing the control board or the terminal board for any reason. For information on the
drive model selection, refer to
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No.
o2-04
n
o2-05: Speed Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the speed reference using the digital operator while in the
Drive Mode.
No.
o2-05
Setting 0: ENTER key required
Every time the speed reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output speed changes immediately when the reference is changed by the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The speed reference is saved for 5 s after it is changed.
n
o2-06: Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 is set to 0.
When the operator is reconnected, the display will indicate that it was disconnected.
No.
o2-06
Setting 0: Continue operation
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an "oPr" fault is triggered. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction in which the motor will rotate after the drive is powered up when the Run command is set to be
given from the operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02 or b1-16 = 0)
No.
o2-07
152
Defaults by Drive Model Selection (o2-04) on page
Name
Drive Model Selection
Name
Speed Reference Setting Method Selection
Name
Digital Operator Disconnection Operation
Name
Motor Direction at Power Up when Using Operator
YASKAWA EUROPE SIEP
249.
Setting Range
Determined by drive
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 or 1
YASKAWA AC Drive L1000V Technical Manual
Default
capacity
Default
0
Default
0
Default
0