N: Advanced Performance Set-Up - YASKAWA L1000V Technical Manual

200/400 v classes: 4.0 to 15 kw
Hide thumbs Also See for L1000V:
Table of Contents

Advertisement

B.3 Parameter Table
No. (Addr.)
Name
L8-88
Safe Disable Operation Mode
(2F5H)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Default setting is determined by the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
u n: Advanced Performance Set-Up
The n parameters are used to adjust more advanced performance characteristics.
n
n2: Speed Feedback Detection Control (AFR) Tuning
No. (Addr.)
Name
n2-01
Speed Feedback Detection Control
(584H)
(AFR) Gain
n2-02
Speed Feedback Detection Control
(585H)
(AFR) Time Constant 1
n2-03
Speed Feedback Detection Control
(586H)
(AFR) Time Constant 2
n
n6: Online Tuning
No. (Addr.)
Name
n6-01
Online Tuning Selection
(570H)
u o: Operator Related Parameters
The o parameters set up the digital operator displays.
n
o1: Digital Operator Display Selection
No. (Addr.)
Name
o1-01
(500H)
Drive Mode Unit Monitor
Selection
o1-02
(501H)
User Monitor Selection after
Power Up
o1-03
Digital Operator Display Unit
(502H)
Selection
o1-10
User-Set Display Units Maximum
(520H)
Value
o1-11
User-Set Display Units Decimal
(521H)
Display
<20> This parameter appears when the drive displays user-set units (o1-03 = 3).
238
All Modes
0: Mode 0 (conventional)
1: Mode 1 (L7 compatible)
V/f
OLV
Sets the internal speed feedback detection control gain in the automatic frequency regulator
(AFR).
If hunting occurs, increase the set value. If response is low, decrease the set value.
V/f
OLV
Sets the time constant used for speed feedback detection control (AFR).
V/f
OLV
Sets the AFR time constant to be used during regen.
V/f
OLV
0: Disabled
1: Enabled
All Modes
Selects the content of the last monitor that is shown when scrolling through Drive Mode
display. Enter the last three digits of the monitor parameter number to be displayed: U -
All Modes
1: Speed reference (U1-01)
2: Direction
3: Output speed (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
All Modes
Sets the units the drive should use to display the frequency reference and motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04, or E5-04)
3: User-selected units (set by o1-10 and o1-11)
All Modes
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
YASKAWA EUROPE SIEP
Description
Description
Description
Description
Setting
common_
Default: 1
TMonly
Min: 0
Max: 1
Setting
common_
TMonly
Default: 1.00
Min: 0.00
Max: 10.00
common_
Default: 50 ms
TMonly
Min: 0 ms
Max: 2000 ms
common_
Default: 750 ms
TMonly
Min: 0 ms
Max: 2000 ms
Setting
common_
Default: 1
TMonly
Min: 0
Max: 1
Setting
Default: 106 (Monitor
common_
TMonly
U1-06)
Min: 105
.
Max: 699
common_
TMonly
Default: 1
Min: 1
Max: 5
common_
TMonly
Default: 1
Min: 0
Max: 3
Default:
<20>
common_
Min: 1
TMonly
Max: 60000
Default:
<20>
Min: 0
Max: 3