3.7 Control Circuit Wiring
n
Wire Size
WARNING! Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in
death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause
erroneous equipment operation.
Select appropriate wire type and gauges from
wire ends. Refer to
Table 3.8
Terminal
S1 to S7, SC, AC, AM, P1-PC, HC,
H1, MA, MB, MC, MD, ME, MF
n
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire
ends with insulated sleeves before connecting to the drive. Refer to
Figure 3.14
2
Size mm
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
u Wiring the Control Circuit Terminal
This section describes the proper procedures and preparations for wiring the control terminals.
WARNING! Sudden Movement Hazard. Operating a drive with untested emergency circuits could result in death or serious injury.
Verify all emergency stop wiring and circuits before operating the drive.
WARNING! Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in
death or serious injury by fire due to overheating of electrical connections.
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could
result in death or serious injury.
WARNING! Electrical Shock Hazard. Before servicing, disconnect all power to the equipment and lock out the power source. Failure to
comply may result in injury from electrical shock. Wait at least five minutes after all indicators are OFF and measure the DC bus
voltage level and main circuit terminals to confirm the circuit is safe before wiring.
WARNING! Sudden Movement and Hazard. Install additional emergency stop circuits separately from the drive emergency circuits.
Failure to comply may result in personal injury.
NOTICE: Equipment Hazard. Do not connect control circuit ground terminals to the drive enclosure. Improper drive grounding can
cause control circuit malfunction.
NOTICE: Equipment Hazard. Insulate shields with heat shrink tubing or tape to prevent contact with other signal lines and equipment.
Improper wiring practices could result in drive or equipment malfunction due to short circuit.
NOTICE: Equipment Hazard. Use twisted-pair or shielded twisted-pair cables for control circuits. Improper wiring practices could result
in drive or equipment malfunction or nuisance trips.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive
or equipment malfunction or nuisance trips.
56
Table
for ferrule terminal types and sizes.
Table 3.7 Wire Gauges
Tightening
Bare Wire Terminal
Torque
Applicable wire size
N m
2
mm
(AWG)
(lb.in.)
Stranded wire:
0.22 to 0.25
0.25 to 1.0 (24 to 17)
(1.9 to 2.2)
Solid wire:
0.25 to 1.5 (24 to 16)
Figure 3.13 Ferrule Dimensions
Table 3.8 Ferrule Terminal Types and Sizes
Type
L (mm)
AI 0.25-8YE
12.5
AI 0.34-8TQ
10.5
AI 0.5-8WH or
14
AI 0.5-8OG
YASKAWA EUROPE SIEP
3.7. For simpler and more reliable wiring, use crimp ferrules on the
Recommended wire size
Applicable wire size
2
mm
(AWG)
mm
0.75
0.25 to 0.5
(18)
Table 3.8
Y E
d1
d2
d1 (mm)
d2 (mm)
0.8
1.8
0.8
1.8
1.1
2.5
Ferrule-Type Terminal
Recommended wire size
2
2
(AWG)
mm
(AWG)
0.5
(24 to 20)
(20)
for dimensions.
Manufacturer
PHOENIX CONTACT
YASKAWA AC Drive L1000V Technical Manual
Wire Type
Shielded wire, etc.