7.5 Drive Replacement
Push down the installation pin on the terminal board with a screwdriver.
3.
Figure 7.9
While holding down the locking pin from step 3, slide the removable terminal block in the direction of the arrows.
4.
Figure 7.10
Replace the drive and wire the main circuit.
5.
n
Terminal Board Replacement
Replace the removable terminal block on the new drive.
1.
Ensure the terminal block is firmly fastened to the connector and that the locking pin is in place.
2.
Connect the blue ground cable from the drive to the ground pin on the terminal board.
3.
Put the front cover back in place and tighten the screw on the front of the drive.
4.
After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If
5.
an oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting
parameter A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through
o4-12 to 0, and parameter o4-13 to 1.
202
CN1
AM AC RP AC
S7 HC SC H1 PC P1
S1
S2 S3 S4 S5 S6
MD
ME
MF
MA MB
MC
Figure 7.9 Terminal Board Locking Pin
CN1
AM AC RP AC
S7 HC SC H1 PC P1
S2 S3 S4 S5 S6
ME
MF
S1
MD
Figure 7.10 Terminal Board Removal
YASKAWA EUROPE SIEP
Push down
the terminal
board locking
pin with a
screwdriver.
MA MB
MC