6.
Drive returns to the parameter display.
7.
Press
and scroll to A1-01.
8.
Press
to display the value set to A1-01. If the first "0" blinks, parameter settings are unlocked.
Use
,
and
9.
10.
Press
to save the setting, or press
11.
The display automatically returns to the parameter display.
Note: Parameter settings can be edited after entering the correct password. Performing a 2-wire initialization resets the password to
"0000". Reenter the password to parameter A1-05 after drive initialization.
u A2: User Parameters
n
A2-01 to A2-32: User Parameters 1 to 32
The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access
by eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited
parameters.
No.
A2-01 to A2-32
Saving User Parameters
To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then
enter the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01
to 1 to restrict access so users can only set and refer to the parameters saved as User Parameters.
n
A2-33: User Parameter Automatic Selection
Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for
quicker access.
No.
A2-33
Setting 0: Do not save list of recently viewed parameters.
Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save history of recently viewed parameters.
Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are
saved with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the
User Parameters using the Setup Mode of the digital operator.
YASKAWA EUROPE SIEP
Step
to change the value if desired.
to return to the previous display without saving changes.
Parameter Name
User Parameters 1 to 32
Parameter Name
User Parameter Automatic Selection
YASKAWA AC Drive L1000V Technical Manual
5.1 A: Initialization
Display/Result
Setting Range
Default
A1-00 to o4-13
Determined by A1-02
Setting Range
Default
0 or 1
1
5
105