6.3 Fault Detection
A general purpose motor is driven below the rated speed
with too high load.
The output voltage is too high.
The wrong motor rated current is set to E2-01.
The maximum output speed is set incorrectly.
Multiple motors are running off the same drive.
The electrical thermal protection characteristics and
motor overload characteristics do not match.
The electrical thermal relay is operating at the wrong
level.
Output current fluctuation due to input phase loss
Digital Operator Display
Cause
Load is too heavy.
Accel/decel ramp is too short.
The output voltage is too high.
Drive capacity is too small.
Overload occurred when operating at low speeds.
Excessive torque compensation.
Output current fluctuation due to input phase loss
Digital Operator Display
Cause
Parameter settings are not appropriate for the load.
Fault on the machine side (e.g., machine is locked up).
Digital Operator Display
Cause
Parameter settings are not appropriate for the load.
Digital Operator Display
Cause
External operator is not properly connected to the drive.
Digital Operator Display
Cause
Overshoot is occurring.
Inappropriate parameter settings.
Digital Operator Display
Cause
Deceleration ramp is too short and regenerative energy
is flowing from the motor into the drive.
Fast acceleration ramp causes the motor to overshoot the
speed reference.
Surge voltage entering from the drive input power.
174
• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor specifically designed to
operate in the desired speed range.
• Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
• Check the motor-rated current.
• Enter the value written on the motor nameplate to parameter E2-01.
• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).
Disable the motor protection function (L1-01 = 0) and install a thermal relay to each motor.
• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.
• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).
Check the power supply for phase loss.
Drive Overload
oL2
The thermal sensor of the drive triggered overload protection.
Reduce the load.
Increase the settings for the acceleration and deceleration times (C1-01 through C1-08).
• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not lower E1-08 and E1-10 excessively. This reduces load tolerance at low speeds.
Replace the drive with a larger model.
• Reduce the load when operating at low speeds.
• Replace the drive with a model that is one frame size larger.
• Lower the carrier frequency (C6-03).
Reduce the torque compensation gain (C4-01) until there is no speed loss but less current.
Check the power supply for phase loss.
Overtorque Detection 1
oL3
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Check the settings of parameters L6-02 and L6-03.
Check the status of the load. Remove the cause of the fault.
Overtorque Detection 2
oL4
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time (L6-06).
Check the settings of parameters L6-05 and L6-06.
External Digital Operator Connection Fault
• The external operator has been disconnected from the drive.
oPr
Note: An oPr fault will occur when all of the following conditions are true:
• Output is interrupted when the operator is disconnected (o2-06 = 1).
• The Up/Down command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
• Check the connection between the operator and the drive.
• Replace the cable if damaged.
• Turn off the drive input power and disconnect the operator. Then reconnect the operator and turn the drive input power back on.
Overspeed (for Control Mode with Encoder)
oS
The motor speed feedback exceeded the F1-08 setting.
Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1).
Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).
DC Bus Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
ov
• For 200 V class: approximately 410 V
• For 400 V class: approximately 820 V
• Increase the deceleration ramp (C1-02, C1-04, C1-06, C1-08).
• Make sure the braking resistor rating/external braking transistor rating fits the application.
• If an external braking transistor is used, make sure it is connected properly and working as expected.
• Check if sudden drive acceleration triggers an overvoltage alarm.
• Increase the acceleration ramp (C1-01, C1-03, C1-05, C1-07).
• Increase the jerk setting in C2-02 (decrease if o1-03 > 3)
Install a DC reactor.
Note: Voltage surge can result from a thyristor convertor and phase advancing capacitor using the same input power supply.
YASKAWA EUROPE SIEP
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
YASKAWA AC Drive L1000V Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents