YASKAWA L1000V Technical Manual page 103

200/400 v classes: 4.0 to 15 kw
Hide thumbs Also See for L1000V:
Table of Contents

Advertisement

Setting 2: Open Loop Vector Control
Use this mode for general, variable-speed applications that require precise speed control, quick torque response, and high
torque at low speed without using a speed feedback signal from the motor.
Note: To set up single channel encoder feedback to the drive usnig the pulse train input for simple closed loop control,
Pulse Train Input on page
n
A1-03: Initialize Parameters
Resets parameters back to the original default values. After initialization, the setting for A1-03 automatically returns to 0.
No.
A1-03
Setting 0: No initialization
Setting 1110: User Initialize
Drive parameters are reset to values selected by the user as User Settings. User Settings are stored when parameter o2-03
is set to "1: Set defaults".
Note: User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03
to 2 to clear the user-defined default values.
Setting 2220: 2-Wire Initialization
Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as Forward run and
Reverse run, respectively.
Setting 5550: oPE04 Reset
An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is
installed in a drive that has edited parameters. Set A1-02 to 5550 to use the parameter settings saved to the terminal block
memory.
Notes on Parameter Initialization
The parameters shown in
Although the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application
preset is selected.
No.
A1-00
A1-02
E1-03
L8-35
o2-04
n
A1-04, A1-05: Password and Password Setting
Parameter A1-04 enters the password when the drive is locked; parameter A1-05 is a hidden parameter that sets the
password.
No.
A1-04
A1-05
How to use the Password
The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to
unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following
parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01,
A1-02, A1-03, A1-06, and A2-01 through A2-33.
The instructions below demonstrate how to set password "1234". An explanation follows on how to enter that password
to unlock the parameters.
YASKAWA EUROPE SIEP
135.
Parameter Name
Initialize Parameters
Table 5.1
will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330.
Table 5.1 Parameters not Changed by Drive Initialization
Parameter Name
Password
Password Setting
YASKAWA AC Drive L1000V Technical Manual
Setting Range
0, 1110, 2220, 5550
Parameter Name
Language Selection
Control Method Selection
V/f Pattern Selection
Installation Selection
Drive Model Selection
Setting Range
0000 to 9999
5.1 A: Initialization
Refer to H6:
Default
0
5
Default
0000
103