No.(Addr.)
Name
d1-26
(2C8H)
Leveling Speed
d1-28
Leveling Speed Detection Level
(2CAH)
d1-29
Inspection Speed Detection Level
(2CBH)
<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to
Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 250
<10> Setting range is limited by the maximum output frequency (E1-04).
u E: Motor Parameters
n
E1: V/f Pattern
No.(Addr.)
Name
E1-01
Input Voltage Setting
(300H)
E1-04
Maximum Output Frequency
(303H)
E1-05
Maximum Voltage
(304H)
E1-06
Base Frequency
(305H)
E1-07
Middle Output Frequency
(306H)
E1-08
Middle Output Frequency Voltage
(307H)
E1-09
Minimum Output Frequency
(308H)
E1-10
Minimum Output Frequency
(309H)
Voltage
E1-11
(30AH)
Middle Output Frequency 2
<11>
E1-12
(30BH)
Middle Output Frequency Voltage 2
<11>
E1-13
Base Voltage
(30CH)
<2> Default setting is dependent on the control mode (A1-02) and the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<11> Parameter is ignored when E1-11 and E1-12 are set to 0.0.
<13> Auto-Tuning will set E1-13 to the same value as E1-05.
n
E2: Motor Parameters
No.(Addr.)
Name
E2-01
Motor Rated Current
(30EH)
E2-02
Motor Rated Slip
(30FH)
YASKAWA EUROPE SIEP
All Modes
Sets leveling speed reference when d1-18 = 1 or 2.
All Modes
Used when d1-18 = 0. If the speed reference selected is lower than d1-28, then the drive uses the
leveling speed as the speed reference.
All Modes
Used when d1-18 = 0. If the speed reference selected is higher than d1-28 but lower or equal to
d1-29, then the drive uses inspection speed as the speed reference.
All Modes
This parameter must be set to the power supply voltage.
WARNING! Electrical Shock Hazard. Drive input voltage (not motor voltage) must be set in
E1-01 for the protective features of the drive to function properly. Failure to do so may result in
equipment damage and/or death or personal injury.
All Modes
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the
setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these
rules:
E1-09 ≤ E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above conditions do not
apply.
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
All Modes
Sets the motor nameplate full load current in Amps. Automatically set during Auto-Tuning.
All Modes
Sets the motor rated slip. Automatically set during Auto-Tuning.
YASKAWA AC Drive L1000V Technical Manual
Description
Description
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Description
B.3 Parameter Table
Setting
Page
Default: 4.00 Hz
<6>
common_
Min: 0.00 Hz
TMonly
118
Max: 120.00 Hz
<6> <10>
common_
TMonly
118
Default: 0.00 Hz
<6>
Min: 0.00 Hz
Max: 120.00 Hz
common_
TMonly
<6> <10>
118
Setting
Page
common_
TMonly
Default: 200 V
<9>
Min: 155 V
119
Max: 255 V
<9>
Default:
<5>
Min: 0.0 Hz
119
Max: 120.0 Hz
Default:190.0 V
<9>
common_
Min: 0.0 V
119
TMonly
Max: 255.0 V
<9>
Default:
<5>
Min: 0.0 Hz
119
Max: 120.0 Hz
Default:
<5>
Min: 0.0 Hz
119
Max: 120.0 Hz
Default:
<2> <9>
Min: 0.0 V
119
Max: 255.0 V
<9>
Default:
<5>
Min: 0.0 Hz
119
Max: 120.0 Hz
Default:
<2> <9>
Min: 0.0 V
119
Max: 255.0 V
<9>
Default: 0.0 Hz
Min: 0.0 Hz
119
Max: 120.0 Hz
Default: 0.0 V
<9>
Min: 0.0 V
119
Max: 255.0 V
<9>
Default: 0.0 V
<9> <13>
119
Min: 0.0 V
Max: 255.0 V
<9>
Setting
Page
Default:
<4>
Min: 10% of drive rated
common_
TMonly
current
120
Max: 200% of drive
rated current
Default:
common_
<4>
TMonly
Min: 0.00 Hz
120
Max: 20.00 Hz
B
229