S6-02: Starting Current Error (SE2) Detection Delay Time
Sets a delay time for starting current error (SE2). SE2 is detected when the drive output current is below 25% after the
Up/Down command has been entered and the brake release time and the time set to S6-02 have both passed. The brake
control command will not be issued (brake stays applied).
No.
S6-02
n
S6-04: Output Current Error (SE3) Detection Delay Time
Sets a delay time for detecting an output current fault (SE3). SE3 is detected when the drive output current drops below
25% after the brake has released.
No.
S6-04
n
S6-05: Brake Response Error (SE4) Detection Time
Sets a delay time for detecting a brake response error (SE4). SE4 is detected when an output terminal set for "Brake
release" (H2-
= 50) and an input terminal set for "Brake feedback" (H1-
05.
No.
S6-05
n
S6-15: Speed Reference Loss Detection
Enabled or disables detection for missing speed reference (FrL).
No.
S6-15
0: Disabled
1: Enabled
n
S6-16: Restart after Baseblock Selection
Allows the drive to restart the motor after returning to normal operation from Baseblock state (H1-
Safe Torque-Off state (Safe Disable inputs H1 and H2 enabled) while the Up/Down command is still active.
No.
S6-16
0: No restart after Baseblock or Safe Torque-Off
Do not restart the motor when leaving the Baseblock or Safe Torque-Off state even if an Up/Down command is still
active.
1: Restart after Baseblock or Safe Torque-Off
Restart when the Up/Down command is still active while the Baseblock or Safe Torque-Off state is left. To use this
function with the Safe Disable function, parameter L8-88 must be set to 1.
n
S6-20: Operation Selection at Rollback (RBK)
Sets the drive stopping method when a rollback (RBK) fault is triggered.
No.
S6-20
0: Ramp to Stop
The drive decelerates to stop with the active deceleration time.
1: Coast to Stop
The motor will coast to stop and the brake control output terminal will immediately open, closing the brake.
YASKAWA EUROPE SIEP
Parameter Name
Starting Current Error (SE2) Detection Delay Time
Parameter Name
Output Current Error (SE3) Detection Delay Time
Parameter Name
Brake Response Error (SE4) Detection Time
Parameter Name
Speed Reference Loss Detection
Parameter Name
Restart after Baseblock Selection
Parameter Name
Operation Selection at Rollback (RBK)
YASKAWA AC Drive L1000V Technical Manual
5.11 S: Elevator Parameters
Setting Range
0.00 to [S1-04 - S1-06]
Setting Range
0 to 5000 ms
= 79) do match for the time set to S6-
Setting Range
0 to 10000 ms
Setting Range
0 or 1
= 8/9) or from
Setting Range
0 or 1
Setting Range
0 to 5
Default
200 ms
Default
200 ms
Default
500 ms
Default
1
Default
0
5
Default
4
159