CPF Instructions
Quantum Scalar i6000 User's Guide
[11:0:2:0] tape
st1 /dev/sg4
If the drive hosting the library control path fails, or the link from switch
port 1 to the hosting drive fails, the control path failover drive would
take over and the switch would detect the media changer device no
longer on port 1, but port 2:
[11:0:1:0] mediumx
sg3
[11:0:2:0] tape
st1 /dev/sg
Note: The control path drive and control path failover settings are
configured on the same screen. You do not need an SNW
license to configure a drive as a control path (see
an HP LTO-5 or LTO-6 Drive as the Control Path
However, you do need an SNW license to configure control
path failover.
1 Log on as an administrator.
2 Access the appropriate screen in one of two ways:
• From the SNW Wizard: Select Setup > Drives > Access > SNW
Wizard. Click Next. From the Select Storage Networking Option
screen, select Control Path and click Next. See
Storage Networking Wizard
• Select Setup > Partitions > Control Path from the main
console.
The Storage Networking Partitions dialog box appears, displaying all
partitions that contain drives eligible to be a control path (HP LTO-5
and LTO-6 FC drives connected to an Ethernet Expansion blade).
Chapter 10: Storage Networking
Configuring Control Path Failover
fc:0x500308c09e2c3004,
fc:0x500308c09e2c37ff,
fc:0x500308c09e2c3004,
on page 350.
0x010200
/dev/
0x010201
/dev/
0x010200
/dev/
Configuring
on page 158).
Using the
355