Configuring An Hp Lto-5 Or Lto-6 Drive As The Control Path - Quantum Scalar i6000 User Manual

Hide thumbs Also See for Scalar i6000:
Table of Contents

Advertisement

Chapter 3: Configuring Your Library
Configuring Control Paths
GUI Menu
Procedure
Path
References
Setup >
Using the Storage
Drives >
Networking Wizard
Access >
on page 350
SNW Wizard
~OR~
~OR~
Setup >
Configuring
Partitions >
Control Paths
Control Path
page 155
Setup >
Licensing Drives for
Drives >
Storage
Access >
Networking
SNW Wizard
page 351
Setup >
Configuring
Drives >
Control Path
Access >
Failover
SNW Wizard
page 353
a.Only HP LTO-5 or LTO-6 drives support control path bridging.
b.Only HP LTO-5 or LTO-6 Storage Networking licensed drives can be configured for control path failover. See
Licensing Drives for Storage Networking
Configuring an HP
LTO-5 or LTO-6 Drive as
the Control Path
158
MCB Direct
Connection
on
on
on
on page 351.
You can configure HP LTO-5 or LTO-6 FC drives as the control path for a
partition. The drive must not be connected to an FC I/O blade, but it
must be connected to an Ethernet Expansion blade.
Note: The control path drive and control path failover settings are
configured on the same screen. You do not need an SNW
license to configure a drive for control path. However, you do
need an SNW license to configure control path failover (see
Configuring Control Path Failover
The instructions that follow only describe how to configure a drive as
the control path for a partition. If you would like to configure both the
control path and control path failover, see
HP LTO-5 or
LTO-6 EEB
Direct
FC I/O Blade
Connection
Connection
Step 2
on page 353).
Configuring Control Path
Quantum Scalar i6000 User's Guide
HP LTO-5 or
LTO-6 EEB
Connection w/
a
b
SNW License
Step 2
Step 3
Step 4