12.2 Alarm Displays

12.2.5 Clearing the Alarm History

12.2.5 Clearing the Alarm History

You can clear the alarm history that is recorded in the SERVOPACK.
The alarm history is not cleared when alarms are reset or when the SERVOPACK main circuit
power is turned OFF. You must perform the following procedure.
Preparations
Always check the following before you clear the alarm history.
• The parameters must not be write prohibited.
Applicable Tools
The following table lists the tools that you can use to clear the alarm history and the applicable
tool functions.
Panel Operator
Digital Operator
SigmaWin+
Operating Procedure
Use the following procedure to reset the alarm history.
1.
Click the
maWin+.
2.
Select Display Alarm in the Menu Dialog Box.
The Alarm Display Dialog Box will be displayed.
3.
Click the Alarm History Tab.
4.
Click the Clear Button.
The alarm history will be cleared.
This concludes the procedure to reset the alarm history.
12-42
Tool
Fn006
Fn006
Alarm − Display Alarm
Servo Drive Button in the workspace of the Main Window of the Sig-
Function
Reference
13.4.6
Clear Alarm History (Fn006)
Σ
-7-Series Digital Operator Operating Manual
(Manual No.: SIEP S800001 33)
on page 12-42
Operating Procedure
on page 13-16