20.5.4 Refrigerant piping

(1) Precautions no refrigerant piping work for prevention against compressor lock
Compressor trouble including lock and motor burn-out is due to faulty parts but mainly concerned in installation and refrigerant
piping conditions, The precautions for refrigerant piping are as belows.
(a) Be sure to perform brazing while flowing nitrogen.
1)
Without flowing nitrogen gas, a lot of oxide film (CU
brazed portions, oxide film is so much generated that this causes a fatal failure in the air conditioning system.
2)
A foreign material (oxide film) causes clogging of the capillary tube or expansion valve, leading to non-cooling (non-
heating), abnormal discharge temperature, compressor lock due to a faulty oil return. In some cases, a lot of foreign
materials block the oil return hole of the accumulator, thereby causing a compressor lock. (This lock trouble may occur
repeatedly 2 or 3 times.)
(b) Don't admit water (waterdrops, condensation) into the piping.
1)
Use a copper piping that is free from water (waterdrops,
condensation).
2)
Don't perform refrigerant piping work while it rains.
3)
To suspend outdoor piping work, perform curing to prevent
water admission.
Bad effects of water
Capillary tube and expansion valve clogging
Refrigerant hydrolysis → "Acid" generation
→ Iron/copper corrosion
Crystal foreign material (clathrate compound)
generation resulting from reaction on refrigerating
machine oil
(c) Don't admit dust or foreign particles in the pipe.
Various foreign particles are included in air conditioners that caused trouble. Be careful about them.
(Concrete fragments, cement, sand, paint, metal powder (copper refuse after deburring, etc.), etc.
(d) Adopt the specified dimensions for pipes.
Too thick:
Too long (L):
(e) Be sure to support the refrigerant piping with support fittings.
1)
The pipe vibrates and expands/shinks during operation. Without proper supports, a load is concentrated partially and
cracks and collapse occur on the piping, thereby causing a unit failure.
2)
A support should be provided at intervals of 2 or 3 m so as not to partially concentrate a load.
O) is generated. In particular, in case of for building with many
2
Improper charge volume
Faulty oil return (insufficient gas flow rate)
Overcharge
Liquid back
Faulty oil return
There will be directly conected to serious
trouble such as compressor lock or burn-
out of the compressor motor.
Compressor lock
Compressor lock
FDC-HKXR
1051