The terminal blocks that plug into the alarm relay contacts are supplied with the router.
They accept wire of any gauge between 28-AWG and 14-AWG (0.08 and 2.08 mm
which is not provided. Use the gauge of wire appropriate for the external device you are
connecting.
To connect an external device to an alarm relay contact:
Prepare the required length of wire with gauge between 28-AWG and 14-AWG (0.08
1.
2
and 2.08 mm
).
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
2.
the strap to one of the ESD points on the chassis.
While the terminal block is not plugged into the relay contact, use a 2.5-mm flat-blade
3.
screwdriver to loosen the small screws on its side. With the small screws on its side
facing left, insert wires into the slots in the front of the block based on the wiring for
the external device. Tighten the screws to secure the wire.
Orient the terminal block according to the labels to the left of the appropriate relay
4.
contact (
means "normally closed,
NC
open").
Plug the terminal block into the relay contact and use a 2.5-mm flat-blade screwdriver
5.
to tighten the screws on the face of the block.
Attach the other end of the wires to the external device.
6.
If attaching a reporting device for the other kind of alarm, repeat the procedure.
T320 Site Preparation Checklist Requirements on page 89
Connecting the T320 Grounding Cable on page 151
T320 General Electrical Safety Guidelines and Electrical Codes on page 353