Power Considerations: SMX Chassis

Use the following wiring specifications for applications including the SMX chassis.
1184514L1

Power Wiring and Fusing

Wiring and fusing should conform to the following:
–48 VDC input and return connections should be provided from the fuse panel using
insulated 14 to 16 AWG wire (16 AWG recommended) for 5 amp fuses.
±24 VDC input and return connections should be provided from the fuse panel using
insulated 14 to 18 AWG wire (16 AWG recommended) for 10 amp fuses.
CAUTION
!
Applications requiring the OMM48 (P/N 1184548L1) cannot be
supplied with ±24 VDC power. The OMM48 only supports –48 VDC.
Separate wires should be run from the fuse panel for each input and return.
Power wire with red insulation is recommended for the input feeds.
Power wire with black insulation is recommended for the return feeds.
If the SMX chassis is to be equipped with a fan assembly, then separate –48 VDC or ±24
VDC power wiring is required for the fan unit.
A fan assembly should be dual-feed powered from different sources than the chassis, using
16 AWG wire from the fuse panel. Follow the same color scheme used to wire the chassis.
The fan assembly (SFANM) should be furnished with a separate 0.5 amp fuse for –48 VDC
or a 1.0 amp fuse for ±24 VDC on each power feed.
61184500L1-5L
Input
DS-1 Terminations
MS3, MS4 A (IN)
SEC IN
T
3
2
1
R
IN
IN
IN
S
MS3/
MS4
T
3
2
1
R
OUT
OUT
OUT
S
SEC OUT
MS3, MS4 B (OUT)
DS-3 Terminations
Output

Figure 6. SMX Chassis Rear-Panel Connections

RS-485, ENVIR Alarms
P8
P15
P7
UNIT MAY BE POWERED BY MULTIPLE SOURCES,
CLOCK
PRI IN
DISCONNECT ALL SOURCES PRIOR TO SERVICING
T
3
2
R
IN
IN
S
MS1/
MS2
T
3
2
R
OUT
OUT
S
CLOCK
PRI OUT
X.25/ADMIN
Clock
X.25/ADMIN
Preparing for Chassis Installation
Power
IN
RET
IN
RET
A
B
-48V
.....
, 3A
.....,
1
+ -24V
/
6A
IN
USE COPPER CONDUCTORS ONLY
1
OUT
ENET
Ethernet
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents