Condition : Air conditioning system periodically repeats proper and improper function.
Symptom
During operation, pressure on low
pressure side cycles between nor-
mal and vacuum
AVENSIS REPAIR MANUAL (RM1018E)
HEATER & AIR CONDITIONER
(1)
Gauge reading:
Low pressure side:
0.15 – 0.25 MPa (1.5 – 2.5 kgf/cm
High pressure side:
1.37 – 1.57 MPa (14 – 16 kgf/cm
E50573
(2)
Probable cause
Moisture in refrigeration system
freezes at expansion valve orifice,
causing a temporary stop of cycle.
However, when it melts, normal
state is restored
http://vnx.su
REFRIGERANT
When the refrigerant volume is proper:
When there is moisture in the refrigeration system:
Diagnosis
Y Drier is overly saturated
Y Moisture in refrigeration system
freezes at expansion valve orifice
and blocks circulation of refriger-
ant
2
)
2)
I22117
Remedy
(1) Replace cooler drier
(2) Remove moisture in cycle by
repeatedly vacuuming
(3) Supply proper amount of new
refrigerant