Alarm Troubleshooting
Resetting the active control card switches control to the standby control card. If the alarm clears when the node switches
to the standby control card, the user can assume that the previously active card is the cause of the alarm.
Step 9
If the control card reset does not clear the alarm, delete the problematic RS-DCC termination by completing the following
steps:
a) From card view, click View > Go to Previous View if you have not already done so.
b) Click the Provisioning > Comm Channels > RS-DCC tabs.
c) Highlight the problematic DCC termination.
d) Click Delete.
e) Click Yes in the Confirmation Dialog box.
Step 10
Recreate the RS-DCC termination. Refer to the Turn Up Network chapter in the Configuration guide for procedures.
Step 11
Verify that both ends of the DCC have been recreated at the optical ports.
If the condition does not clear, log into the Technical Support Website at
index.html
for more information or call Cisco TAC (1 800 553-2447).
If the Technical Support technician tells you to reseat the card, complete the
, on page 452
procedure. If the Technical Support technician tells you to remove the card and reinstall a new one, follow
the
Physically Replace a Card, on page 453

RS-TIM

Default Severity: Critical (CR), Service-Affecting (SA)
Logical Object: STMN
The Regenerator Section TIM alarm occurs when the expected J0 path trace string does not match the received
string.
If the alarm occurs on a port that has been operating with no alarms, the circuit path has changed or someone
entered a new incorrect value into the Current Transmit String field. Follow the procedure below to clear
either instance.
Clear the RS-TIM Alarm
SUMMARY STEPS
1. Complete the
DETAILED STEPS
Complete the
Clear the TIM Alarm, on page 415
If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical Support
Website at
http://www.cisco.com/c/en/us/support/index.html
procedure.
Clear the TIM Alarm, on page 415
procedure for the J0 byte.
Cisco NCS 2000 series Troubleshooting Guide, Release 11.0
http://www.cisco.com/c/en/us/support/
Remove and Reinsert (Reseat) Any Card
procedure for the J0 byte.
for more information or log into
RS-TIM
http://www.cisco.com/c/
383

Advertisement

Table of Contents
loading

Table of Contents