Watch Cycle Time; Cycle Time Monitoring - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Computing the Cycle Time

Watch Cycle Time

PLC Setup
Related Flags
Cycle Time
Monitoring
Related Words
Note
If the cycle time exceeds the watch (maximum) cycle time setting, the Cycle
Time Too Long Flag (A401.08) will be turned ON and PLC operation will be
stopped.
Name
Enable Watch Cycle
0: Default (1 s)
Time Setting
1: User setting
Watch Cycle Time
001 to FA0: 10 to 40,000 ms
(10-ms increments)
Name
Address
Cycle Time Too Long
A401.08
Flag
The maximum cycle time is stored in A262 and A263 and the present cycle
time is stored in A264 and A265 every cycle.
Name
Addresses
Maximum Cycle
A262 and
Time
A263
Present Cycle Time
A264 and
A265
The average cycle time for the past eight cycles can be read from the CX-Pro-
grammer.
The following methods are effective in reducing the cycle time.
• Place tasks that do not need to be executed on standby.
• Use JMP-JME instructions to skip instructions that do not need to be exe-
cuted.
Settings
0000 hex: Watch cycle time of
1 s
Description
Turns ON if the present cycle time exceeds the
Watch Cycle Time set in the PLC Setup.
Description
These words contain the maximum cycle time in
increments of 0.1 ms. The time is updated every
cycle and is recorded in 32-bit binary (0 to FFFF
FFFF hex, or 0 to 429,496,729.5 ms). (A263 is
the leftmost word.)
These words contain the present cycle time in
increments of 0.1 ms. The time is updated every
cycle and is recorded in 32-bit binary (0 to FFFF
FFFF, or 0 to 429,496,729.5 ms). (A265 is the
leftmost word.)
Section 2-7
Default
63