Socket Services
Bit
Switch
8
0
UDP Open Request
Switch
9
1
TCP Passive Open
Request Switch
10
2
TCP Active Open
Request Switch
11
3
Send Request
Switch
12
4
Receive Request
Switch
13
5
Close Request
Switch
14
6
Reserved
15
7
Reserved
198
Status Manipulated
by
ON
User
UDP socket opened when switch is turned
ON.
OFF
Unit
Unit turns OFF switch when open processing
has been completed (i.e., when a connection
has been made).
ON
User
Passive TCP socket opened when switch is
turned ON.
OFF
Unit
Unit turns OFF switch when open processing
has been completed (i.e., when a connection
has been made).
ON
User
Active TCP socket opened when switch is
turned ON.
OFF
Unit
Unit turns OFF switch when open processing
has been completed (i.e., when a connection
has been made).
ON
User
Send processing executed when switch is
turned ON.
(The protocol (TCP/UDP) is determined when
the socket is opened.)
OFF
Unit
Unit turns OFF switch when send processing
has been completed.
ON
User
Receive processing executed when switch is
turned ON.
(The protocol (TCP/UDP) is determined when
the socket is opened.)
OFF
Unit
Unit turns OFF switch when receive process-
ing has been completed.
ON
User
Close processing executed when switch is
turned ON.
(The protocol (TCP/UDP) is determined when
the socket is opened.)
OFF
Unit
Unit turns OFF switch when close processing
has been completed.
---
---
---
---
---
---