Omron CP1L-EL20DR-D Operation Manual page 552

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Temperature Sensor Units
Note
Creating a Ladder
Program
518
Input 0
Input 1
Input 1
A
A
B
Input 0
Input 0
Input 1
B
B
B
Pt
Pt
Temperature
Temperature
input 0
input 1
Do not connect anything to terminals not used for inputs.
Word Allocations
Temperature Sensor Units are allocated words in the same way as other CP-
series Expansion Units or Expansion I/O Units, in order of connection. A Tem-
perature Sensor Unit is allocated the next input words following the input
words of the CPU Unit or previous Expansion Unit or Expansion I/O Unit. Four
input words are allocated to the 2-input CP1W-TS001 or CP1W-TS101 and
four input words are allocated to the 4-input CP1W-TS002 or CP1W-TS102.
No output words are allocated.
Example 1
CP1L-EM CPU Unit
with 40 I/O points
CIO 0
Input word
CIO 1
addresses
Output word
CIO 100
addresses
CIO 101
Example 2
CP1L-EM CPU Unit
with 40 I/O points
CIO 0
Input word
CIO 1
addresses
Output word
CIO 100
addresses
CIO 101
Converted Temperature Data
The temperature data will be stored in the input words allocated to the Tem-
perature Sensor Unit in 4-digit hexadecimal.
TS002/TS102
m+1
Converted temperature data from input 0
m+2
Converted temperature data from input 1
m+3
Converted temperature data from input 2
m+4
Converted temperature data from input 3
Input 2
Input 3
Input 3
NC
A
A
B
NC
Input 2
Input 2
Input 3
B
B
B
Pt
Pt
Temperature
Temperature
input 2
input 3
CP1W-TS001/101
Temperature Sensor Unit
CIO 2
CIO 3
None
CP1W-TS002/102
Temperature Sensor Unit
CIO 2
CIO 3
CIO 4
CIO 5
None
TS001/TS101
m+1
Converted temperature data from input 0
m+2
Converted temperature data from input 1
Section 9-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents