Remote Ip Address; Remote Udp/Tcp Port No; Time Out Time - Omron CP1L-EL20DR-D Operation Manual

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Socket Services

Remote IP Address

Remote UDP/TCP Port No.

Time Out Time

202
Specify the IP address of the remote device.
• Offset +2 in the Socket Service Parameter Area contains the upper bytes
of the Remote IP Address, and offset +3 contains the lower bytes.
Example: The contents of offsets +2 and +3 would be as shown below
when the Remote IP Address is 196.36.32.55 (C4.24.20.37 hexadeci-
mal).
+2: C424
+3: 2037
• This parameter is not used when making a receive request for a UDP
socket. The remote IP address will be stored with the response data and
will be written as the Remote IP Address in the Socket Service Parameter
Area.
• When opening a passive TCP socket, the combination of the remote IP
address and the remote TCP port number can be used to affect process-
ing as shown in the following table.
Remote IP
Remote TCP
Address
Port No.
0
0
0
Not 0
Not 0
0
Not 0
Not 0
If the Remote IP Address is set to 0, a connection can be made to any remote
node and the remote IP address of the node that is connected will be stored
as the Remote IP Address in the Socket Service Parameter Area. If a specific
remote IP address is set, then a connection can be made only to the node
with the specified address.
If the Remote TCP Port No. is set to 0, a connection can be made to any
remote node regardless of the TCP port number it is using. If a specific
remote TCP port number is set, then a connection can be made only to a
node using the specified TCP port number.
Specify the UDP or TCP port number used by the remote device.
• This parameter is not used when making a receive request for a UDP
socket. The remote UDP/TCP port number will be stored with the
response data and will be written as the Remote UDP/TCP Port No. in the
Socket Service Parameter Area.
• When opening a passive TCP socket, the combination of the remote IP
address and the remote TCP port number can be used to affect process-
ing as shown in the table for the Remote IP Address, above. If the Remote
UDP/TCP Port No. is set to 0, the UDP/TCP port number of the remote
device will be written as the Remote UDP/TCP Port No. in the Socket Ser-
vice Parameter Area.
Set the time limit in units of 0.1 s for completion of communications from the
time that the Receive Request Switch (TCP or UDP) or the TCP Passive
Open Request Switch is turned ON. A response code of 0080 hexadecimal
(timeout) will be stored if communications time out. If 0 is set, the requested
service will not be timed.
Processing
All connection requests accepted.
Connection requests accepted only for the same
port number.
Connection requests accepted only for the same
IP address.
Connection requests accepted only for the same
port number and IP address.
Section 6-6