Omron CP1L-EL20DR-D Operation Manual page 55

Sysmac cp series cp1l-el/em cpu unit
Table of Contents

Advertisement

Part Names and Functions
ON
1
2
3
4
5
ON
1
2
3
(3) DIP Switch
CPU Units with 30 or 40 I/O Points
No.
Setting
SW1
ON
6
OFF
SW2
ON
OFF
SW3
ON
OFF
SW4
ON
OFF
SW5
ON
OFF
SW6
OFF
Note The following data will be write-protected if pin SW1 is turned ON:
• The entire user program (all tasks)
• All data in parameter areas (such as the PLC Setup)
When SW1 is turned ON, the user program and the data in the pa-
rameter areas will not be cleared even if the All Clear operation is
performed from a Peripheral Device (i.e., the CX-Programmer).
CPU Units with 20 I/O Points
No.
Setting
SW1
ON
4
OFF
SW2
ON
OFF
SW3
ON
OFF
SW4
ON
OFF
Description
User memory write-
Used to prevent pro-
protected (See note.)
grams from being inad-
vertently overwritten.
User memory not
write-protected.
Data automatically
Used to enable pro-
transferred from
grams, Data Memory, or
Memory Cassette at
parameters saved on a
startup.
Memory Cassette to be
opened by the CPU Unit
Data not transferred.
at startup.
A395.12 ON
This pin enables control-
ling a bit in memory with-
A395.12 OFF
out using an input relay.
Used for peripheral
Used to enable a Serial
bus.
Communications Option
Board mounted in Option
According to PLC
Board Slot 1 to be used
Setup.
by the peripheral bus.
Used for peripheral
Used to enable a Serial
bus.
Communications Option
Board mounted in Option
According to PLC
Board Slot 2 to be used
Setup.
by the peripheral bus.
Keep turned OFF.
---
Description
User memory write-
Used to prevent pro-
protected (See note.)
grams from being inad-
vertently overwritten.
User memory not
write-protected.
Data automatically
Used to enable pro-
transferred from
grams, Data Memory, or
Memory Cassette at
parameters saved on a
startup.
Memory Cassette to be
opened by the CPU Unit
Data not transferred.
at startup.
A395.12 ON
This pin enables control-
ling a bit in memory with-
A395.12 OFF
out using an input relay.
Used for peripheral
Used to enable a Serial
bus.
Communications Option
Board mounted in Option
According to PLC
Board Slot 1 to be used
Setup.
by the peripheral bus.
Section 2-1
Application
Default
OFF
OFF
OFF
OFF
OFF
OFF
Application
Default
OFF
OFF
OFF
OFF
21