Power Supply Unit Replacement Time - Omron CJ2 User Manual

Cj series
Hide thumbs Also See for CJ2:
Table of Contents

Advertisement

7 Inspection and Maintenance
7-3
Power Supply Unit Replacement
Time
Principle of Replacement Notification
The Power Supply Unit has a built-in electrolytic capacitor. The electrolytic capacitor is impregnated
with electrolytic solution that starts to penetrate the sealing rubber from the time of manufacture. As
time elapses, the internal electrolytic solution continues to evaporate, resulting in decreased electro-
static capacity and deterioration in other characteristics. Over time, the characteristic deterioration of
the electrolytic capacitor prevents the Power Supply Unit from being utilized to its full capacity. In partic-
ular, the speed at which the electrolytic capacitor deteriorates fluctuates greatly with the ambient tem-
perature (generally, a temperature rise of 10°C will double the rate of a reaction, as stated by Arrhenius'
law).
The CJ1W-PA205C Power Supply Unit with Replacement Notification monitors the internal temperature
of the Power Supply Unit while the power is turned ON, and calculates the level of deterioration of the
electrolytic capacitor from the operating time and internal temperature. The replacement notification
function displays the approximate time until the Power Supply Unit will stop functioning at its full capac-
ity due to the characteristic deterioration of the electrolytic capacitor, based on the calculated level of
deterioration. When 6 months are remaining until replacement is required, the alarm output will turn
OFF.
Note The replacement notification function provides an indication of when the deterioration of the electrolytic
capacitor will prevent the power supply functioning at its full capacity. It does not provide information on fail-
ures occurring due to other causes.
Power Supply Unit with Replacement Notification
Model
CJ1W-PA205C
Power Supply Unit Replacement Notification Module
CJ1W-PA205C
Replacement notification display (7-segment, red)
CJ1W-PA205C
TEST
ALARM OUTPUT
DC30V, 50mA
L
NORMAL:ON
ALARM OFF
7-10
Output capacity: 5 A at 5 VDC, 0.8 A at 24 VDC, total of 30 W
With replacement notification
POWER
POWER indicator (green)
Alarm output (replacement
notification output)
test switch
Alarm output (replacement
notification output)
wiring diagram
Specifications
CJ2 CPU Unit Hardware User's Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1-hCj1mCj1

Table of Contents