Temperature Sensor Units
Startup Operation
After power is turned ON, approximately 1 s is required for the first conversion
data to be stored in the input word. During that period, the data will be 7FFE.
Therefore, create a program as shown below, so that the ladder can start to
operate with valid conversion data in input words.
Always ON
P_On
(P_EQ)
Programming Example
The following programming example shows how to store the input data of
CP1W-TS003 (4 inputs) in D0 to D3, and W10.00 to W10.03 turn ON at the
time of open-circuit detection.
CP1L-EM CPU Unit
with 40 I/O points
CIO 0
Input word
CIO 1
addresses
Output word
CIO 100
addresses
CIO 101
DIP Switch Setting
SW1
OFF
SW2
OFF
SW3
NC
SW4
OFF
SW5
ON
SW6
ON
Wiring Diagram
LOOP0+
LOOP0−
Temperature input 0
Temperature input 1
CMP(020)
Temperature input data
2
output word
#7FFE
Initialization
Completed Flag
1000.00
CP1W-TS003
Temperature Sensor Unit
Temperature unit setting: OFF(ºC)
CIO 2
CIO 3
Input range setting
CIO 4
Input 0: Thermocouple K(CIO2)
CIO 5
Input 1: Thermocouple K(CIO3)
Input 2: Thermocouple K(CIO4)
None
Input 3: Analog input 1 to 5V(CIO5)
K
°C
Thermocouple
Analog
1 to 5V/4 to 20mA
LOOP1+
NC
NC
I IN2
LOOP1−
Cold junction
Temperature
compensator
input 2
Section 9-5
LOOP2+
LOOP3+
I IN3
V IN2
V IN3
LOOP2−
LOOP3−
COM2
COM3
Analog
device
with
voltage
output
Analog
input 3
(1 to 5 V)
535