Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A274
00
High-speed
Counter 0
Range 1 Com-
parison Condi-
tion Met Flag
01
High-speed
Counter 0
Range 2 Com-
parison Condi-
tion Met Flag
02
High-speed
Counter 0
Range 3 Com-
parison Condi-
tion Met Flag
03
High-speed
Counter 0
Range 4 Com-
parison Condi-
tion Met Flag
04
High-speed
Counter 0
Range 5 Com-
parison Condi-
tion Met Flag
05
High-speed
Counter 0
Range 6 Com-
parison Condi-
tion Met Flag
06
High-speed
Counter 0
Range 7 Com-
parison Condi-
tion Met Flag
07
High-speed
Counter 0
Range 8 Com-
parison Condi-
tion Met Flag
08
High-speed
Counter 0
Comparison
In-progress
Flag
09
High-speed
Counter 0
Overflow/
Underflow
Flag
10
High-speed
Counter 0
Count Direc-
tion
Function
These flags indicate whether the PV
is within the specified ranges when
high-speed counter 0 is being oper-
ated in range-comparison mode.
Cleared at beginning of operation.
Cleared when range comparison
table is registered.
OFF: PV not in range
ON: PV in range
This flag indicates whether a com-
parison operation is being executed
for high-speed counter 0.
Cleared at beginning of operation.
OFF: Stopped.
ON: Being executed.
This flag indicates when an overflow
or underflow has occurred in the
high-speed counter 0 PV. (Used with
the linear mode counting range
only.)
Cleared when operation starts.
Cleared when PV is changed.
OFF: Normal
ON: Overflow or underflow
This flag indicates whether the high-
speed counter is currently being
incremented or decremented. The
counter PV for the current cycle is
compared with the PLC in last cycle
to determine the direction.
OFF: Decrementing
ON: Incrementing
Settings
Status
Status
after
at star-
mode
change
---
---
Cleared
---
---
Cleared
---
---
Cleared
---
---
Cleared
Appendix D
Write
Related
timing
flags, set-
tup
tings
Refreshed
---
each cycle
during
oversee
process.
Refreshed
when
PRV(881)
instruction
is exe-
cuted.
Refreshed
---
when com-
parison
operation
starts or
stops.
Refreshed
---
when an
overflow or
underflow
occurs.
Setting
Read only
used for
high-speed
counter,
valid dur-
ing counter
operation.