Memory Cassette Functions
Reading Data from
the Memory Cassette
to the CPU Unit
Precautions when
Using the Memory
Cassette Data
Transfer Function
438
The CX-Programmer's Memory Cassette function can be used to read data
stored on the Memory Cassette, and transfer it to the corresponding areas in
the CPU Unit. The data to be read can be individually specified.
CP1L-EL/EM CPU Unit
SYSMAC
CP1L
Data in CPU
COM
01
03
05
07
09
11
01
03
05
07
09
11
NC
00
02
04
06
08
10
00
02
04
06
08
10
POWER
Unit
RUN
ERR/ALM
INH
LNK/ACT
BKUP
1
2
00
01
02
03
04
06
00
01
03
04
06
ANALOG INPUT
COM(V+)
COM
05
07
COM
02
COM
05
07
V1+ V2+ COM
MAC Address:
01234567890A
Reading
Programs, parameters, DM initial
values, comment memory, etc.
(Can be specified individually.)
This function can be used for operations such as writing the required backup
data to the CPU Unit for maintenance.
• In order for Memory Cassette data to be transferred, the Memory Cas-
sette must be mounted in the CPU Unit.
• The BKUP indicator will light while data is being transferred to or verified
in a Memory Cassette. Never turn OFF the power to the PLC or remove
the Memory Cassette while the BKUP indicator is lit. Doing either may
make it impossible to use the Memory Cassette.
• Memory Cassette data transfers and verification are possible only when
the CPU Unit operating mode is PROGRAM mode. The Memory Cassette
transfer function cannot be used in either RUN or MONITOR mode.
• When using automatic transfer from a Memory Cassette at startup, be
sure to transfer the data to the Memory Cassette if any changes are made
using online editing.
• The operating mode cannot be switched from PROGRAM mode to RUN
or MONITOR mode while a Memory Cassette data transfer or verification
is in progress.
• The following table shows whether data transfers are enabled when the
CPU Unit is protected in various ways.
Type of protection
Not protected.
System protected by DIP switch
pin SW1 set to ON.
Protected by password. Over-
writing and duplication both per-
mitted.
Protected by password. Over-
writing prohibited and duplica-
tion permitted.
CX-Programmer
Reading from Memory
Cassette to CPU Unit
CP1W-ME05M
Memory Cassette
Transfer from CPU Unit
to Memory Cassette
Yes
Yes
Yes
Yes
Section 8-6
Transfer from Memory
Cassette to CPU Unit
Yes
No
Yes
Transfer enabled only at
startup.