Analog Output Units
Procedure
Writing Set Data and
Writing D/A Conversion
Data
■ 4 to 20 mA
When the resolution is 1/6,000, the hexadecimal values 0000 to 1770 (0 to
6000) correspond to an analog current range of 4 to 20 mA.
The entire output range is 3.2 to 20.8 mA.
20.8 mA
FED4
8000
(−300)
When the resolution is 1/12,000, the hexadecimal values 0000 to 2EE0 (0 to
12000) correspond to an analog voltage range of 4 to 20 mA.
The entire output range is 3.2 to 20.8 mA.
20.8 mA
FDA8
8000
(−600)
Connect and wire Units.
Create a ladder program.
■ CP1W-DA041/CP1W-DA042
CPU Unit
Ladder program
MOV(021)
Writes the set data.
Writes the conversion
values.
20 mA
4 mA
3.2 mA
1770
189C
0 mA
(6000)
(6300)
20 mA
4 mA
3.2 mA
2EE0
3138
0 mA
(12000)
(12600)
• Connect Analog Output Units.
• Wire to analog input devices.
• Write set data to output words
CP1W-DA041/DA042: Words (n+1, n+2)
CP1W-DA021: Word (n+1)
• Set use of outputs.
• Select output signals using range codes.
• Write D/A conversion values to output words
CP1W-DA041/DA042: Words (n+1 to n+4)
CP1W-DA021: Words (n+1, n+2)
Analog Output Unit
Word (n+1) Set data (outputs 1, 2)
Word (n+2) Set data (outputs 3, 4)
Word (n+1)
Analog output 1 conversion value
Word (n+2) Analog output 2 conversion value
Word (n+3) Analog output 3 conversion value
Word (n+4) Analog output 4 conversion value
Where "n" is the last output word
allocated to the CPU Unit, or
previous Expansion Unit or
Expansion I/O Unit.
Section 9-3
Conversion
Data
7FFF
Hexadecimal
(Decimal)
Conversion Data
7FFF
Hexadecimal (Decimal)
Analog devices
Adjustment equipment
Servo Controller
Variable speed device
Recorder
Other
477